48 x 96 mm. Large White PV Display That’s Easier to Read. Easy to Use, from Model Selection to Setup and Operation. A Complete Range of I/O Capacities, Functions, and Performance. Handles More Applications. E5EC-B is our Value Design product which increase the value of your control panel.
Specification
Power supply voltage | A in model number: 100 to 240 VAC, 50/60 HzD in model number: 24 VAC, 50/60 Hz; 24 VDC | |
---|---|---|
Operating voltage range | 85 to 110% of rated supply voltage | |
Power consumption | Models with option selection of 000:6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at24 VAC or 2.3 W max. at 24 VDCAll other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 Wmax. at 24 VDC | |
Sensor input | Temperature inputThermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL IIPlatinum resistance thermometer: Pt100 or JPt100Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to260°CAnalog inputCurrent input: 4 to 20 mA or 0 to 20 mAVoltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V | |
Input impedance | Current input: 150 Ω max., Voltage input: 1 MΩ min.(Use a 1:1 connection when connecting the ES2-HB-N/THB-N.) | |
Control method | ON/OFF or 2-PID control (with auto-tuning) | |
Controloutput | Relay output | SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,minimum applicable load: 5 V, 10 mA (reference value) |
Voltage output(for driving SSR) | Output voltage: 12 VDC ± 20% (PNP), max. load current: 40 mA, with short-circuitprotection circuit (The maximum load current is 21 mA for models with two controloutputs.) | |
Linear currentoutput | 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10,000 | |
Auxiliaryoutput | Number of outputs | E5EC: 4E5EC-B: 2 or 4 (depends on model) |
Outputspecifications | SPST-NO. relay outputs, 250 VAC, Models with 2 outputs: 3 A (resistive load),Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (referencevalue) | |
Eventinput | Number of inputs | 2, 4 or 6 (depends on model) |
External contactinputspecifications | Contact input: ON: 1 kΩ max., OFF: 100 kΩ min. | |
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max. | ||
Current flow: Approx. 7 mA per contact | ||
Transferoutput | Number of outputs | 1 (only on models with a transfer output) |
Outputspecifications | Current output: 4 to 20 mA DC, Load: 500 Ω max., Resolution: Approx. 10,000Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., Resolution: Approx. 10,000 | |
Remote SP input | Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.) | |
Potentiometer input * | 100 Ω to 10 kΩ | |
Setting method | Digital setting using front panel keys | |
Indication method | 11-segment digital display and individual indicatorsCharacter height: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mmThree displays Contents: PV/SV/MV, PV/SV/Multi-SP, or PV/SV/Remaining soak time, etcNumbers of digits: 4 digits each for PM, SV, and MV displays | |
Multi SP | Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs,key operations, or serial communications. | |
Bank switching | None | |
Other functions | Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarmfunctions, heater burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100%AT, MV limiter, input digital filter, self tuning, robust tuning, PV input shift, run/stop,protection functions, extraction of square root, MV change rate limit, logic operations,temperature status display, simple programming, moving average of input value, anddisplay brightness setting | |
Ambient operatingtemperature | -10 to 55°C (with no condensation or icing), For 3-year warranty: -10 to 50°C withstandard mounting (with no condensation or icing) | |
Ambient operating humidity | 25 to 85% | |
Storage temperature | -25 to 65°C (with no condensation or icing) | |
Altitude | 2,000 m max. | |
Recommended fuse | T2A, 250 VAC, time-lag, low-breaking capacity | |
Installation environment | Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1) |
Order Code
Models with Screw Terminal Blocks
Models with Push-In Plus Terminal Blocks
Optional Products (Order Separately)
USB-Serial Conversion Cable
Model |
---|
E58-CIFQ2 |
Communications Conversion Cable
Model |
---|
E58-CIFQ2-E |
Terminal Covers (for E5EC)
Model |
---|
E53-COV24 (3pcs) |
Note: The Terminal Covers E53-COV24 are provided with the Digital Temperature Controller.
Waterproof Packing
Model |
---|
Y92S-P9 |
Note: This Waterproof Packing is provided with the Digital Temperature Controller.
Waterproof Cover
Model |
---|
Y92A-49N |
Front Port Cover
Model |
---|
Y92S-P7 |
Note: This Front Port Cover is provided with the Digital Temperature Controller.
Mounting Adapter
Model |
---|
Y92F-51 (2pcs) |
Note: This Mounting Adapter is provided with the Digital Temperature Controller.
Current Transformers (CTs)
Hole diameter | Model |
---|---|
5.8 mm | E54-CT1 |
5.8 mm | E54-CT1L * |
12.0 mm | E54-CT3 |
12.0 mm | E54-CT3L * |
* Lead wires are included with these CTs. If UL certification is required, use these CTs.
CX-Thermo Support Software
Model |
---|
EST2-2C-MV4 |
Model List
E5EC-CX2ABM-000E5EC-CX2ABM-004E5EC-CX2ABM-014E5EC-CX2DBM-000E5EC-CX2DBM-004E5EC-CX2DBM-014E5EC-CX4ABM-000E5EC-CX4ABM-004E5EC-CX4ABM-014E5EC-CX4DBM-000E5EC-CX4DBM-004E5EC-CX4DBM-014E5EC-QX2ABM-000E5EC-QX2ABM-008E5EC-QX2ABM-010E5EC-QX2ABM-011E5EC-QX2DBM-000E5EC-QX2DBM-008E5EC-QX2DBM-010E5EC-QX2DBM-011E5EC-QX4ABM-000E5EC-QX4ABM-008E5EC-QX4ABM-010E5EC-QX4ABM-011E5EC-QX4DBM-000E5EC-QX4DBM-008E5EC-QX4DBM-010E5EC-QX4DBM-011E5EC-RX2ABM-000E5EC-RX2ABM-008E5EC-RX2ABM-010E5EC-RX2ABM-011E5EC-RX2DBM-000E5EC-RX2DBM-008E5EC-RX2DBM-010E5EC-RX2DBM-011E5EC-RX4ABM-000E5EC-RX4ABM-008E5EC-RX4ABM-010E5EC-RX4ABM-011