specification | input |
---|---|
Control system network type | CC-Link |
Number of input/output points | 16 inputs |
Connecting terminal | Spring lock (push-in terminal block) |
Specification
Input section | |
---|---|
Insulation method | photocoupler isolation |
Rated input voltage | DC24V |
Rated input current | about 5 mA |
Working voltage range | 19.2 to 26.4 VDC (ripple rate within 5%) |
ON voltage | 15V or more |
ON current | 3mA or more |
OFF voltage | 3V or less |
OFF voltage | 0.5mA or less |
input resistance | about 4.7 kΩ |
Input format | Sink and source shared type |
Response time (ON→OFF) | 0.2ms or less (at 24VDC) |
Response time (OFF→ON) | 0.2ms or less (at 24VDC) |
Common method | 16 points/common |
---|---|
Number of occupied stations | 32 points per station (16 points used) |
I/O unit power supply (voltage) | 20.4 to 26.4 VDC (ripple rate within 5%) |
I/O unit power supply (current) | 40mA or less (24VDC, when all points are ON) |
Noise tolerance | DC type noise voltage ±900Vp-p, noise width 1μs, noise frequency 45Hz, by noise simulator |
Withstand voltage | 500 VAC for 1 minute between all DC external terminals and ground |
insulation resistance | 500 VDC between all DC external terminals and ground, 10 MΩ or more by insulation resistance tester |
mass | about 145g |
External connection method | 9-pole 2-piece connector (transmission line, unit power terminal, I/O power terminal, COM1, COM2) |